Business guides – contracts, HR, AI & compliance

PFAS firefighting foam – EU REACH phase-out dates and site management plans

A practical EU REACH guide for organisations inventorying PFAS foam, selecting relevant transition dates and documenting replacement.

Published Mallbutiken
PFAS firefighting foam – EU REACH phase-out dates and site management plans

Short answer: Commission Regulation (EU) 2025/1988 added entry 82 to REACH Annex XVII on PFAS firefighting foams. The general placing-on-the-market and use restriction applies from 23 October 2030 to a sum of PFAS of at least 1 mg/L, but key uses have different dates. From 23 October 2026, covered ongoing uses are subject to emission control and a site-specific management plan. Never infer a permitted use from the general 2030 date alone.

Why inventory each site?

Inventory every actual facility or foam system, not merely the company's central purchasing list. Record product, supplier, tank, stock volume, SDS, actual PFAS-sum evidence and site use. Missing analytical data do not establish a fluorine-free product. Separate substances such as PFOS, PFOA, PFHxS and PFHxA may already be subject to tighter REACH or POPs controls.

Deadlines: supply is not the same as use

Use or activityDeadline and required distinction
General placement on market and useBroad restriction from 23 October 2030 for total PFAS at least 1 mg/L, without overriding earlier substance-specific bans.
Portable extinguishers – market placementSpecial dates 23 October 2026, or 23 April 2027 for alcohol-resistant foam; distinguish supply and use.
Portable extinguishers – continued useSeparate deadline 31 December 2030, subject to stricter individual chemical restrictions.
Training and testingUse deadline 23 April 2027; particular functional testing with all releases contained needs separate assessment.
Public or equivalent fire servicesUse deadline 23 April 2027, with a narrowly defined Seveso incident exception.
Specified Seveso sites, offshore and shipsConditional dates up to 23 October 2035 for defined categories. Civil aviation is not automatically included.

What belongs in the site-specific plan?

Where entry 82 paragraph 7 applies, from 23 October 2026 use covered foam only for relevant class B fires, minimise emissions and exposure, collect stocks and PFAS waste where technically and practically possible, and document treatment. Prepare a site-specific management plan listing actual use and volumes, collection and disposal, equipment cleaning and maintenance, accidental spills and substitution of fluorinated foam. Review annually and keep available for inspection for at least 15 years. Do not assert that every premises has this duty.

Labelling and concentration checks

Paragraphs 8–10 prescribe warnings from 23 October 2026 for qualifying foam placed on the market (with an exception for portable extinguishers), and for certain unused stocks and waste. Verify local language, legibility and permanence. The 50 mg/L rule is a specific allowance for fluorine-free foam originating from equipment cleaned with best available techniques; it is not a general foam limit and excludes portable extinguishers.

Six steps for an auditable transition

  1. List each fixed installation, portable extinguisher, stock and contractor-operated foam system by site.
  2. Request PFAS sum evidence, the supplier's declarations and actual use class; mark an unknown concentration as unknown.
  3. Assess supply dates, use dates, labelling, waste and earlier chemical bans separately for each system.
  4. For continued uses subject to paragraph 7, capture class B restriction, emissions, containment, spill response and annual plan review.
  5. Commission qualified fire protection experts to validate fluorine-free alternatives, compatibility and safe system conversion.
  6. Keep real waste collection/treatment records and supporting receipts, maintaining the plan versions and review history.

Two cases that must be separated

Industrial foam tank: A site records 3 mg/L PFAS in a foam tank. Whether Seveso conditions or paragraph 7 apply must be assessed from the real site and use, not assumed from its industrial label.

Portable extinguishers: An organisation holds older PFAS extinguishers. The dates for market supply in October 2026 and use until December 2030 differ; earlier substance prohibitions still require checking.

Frequently asked questions

Does every company need a 15-year management plan?

No. Check whether its actual location and covered use engage paragraph 7.

Was all PFAS foam prohibited on 23 October 2026?

No. That date brings key controls; broader prohibitions and the defined exceptions use other deadlines.

May a documented spreadsheet authorise discharge to the drain?

No. Waste, containment, transport and destruction require their own environmental and legal evaluation.

law · agency · guide · pops · waste

Editorial source review 13 November 2026. This guide is not fire-safety certification, a permit, lab analysis, legal advice or authorisation to dispose of firefighting foam.

Get the editable Word, PDF and Excel package: PFAS fire-fighting foam 2026/2030 – management plan, spills & foam replacement | Word/PDF/Excel. Check the product description for its precise contents.

Read also PFAS in a private well in Sweden – PFAS4, PFAS21, test results and retesting. Firefighting foam can be a source of PFAS contamination in groundwater. Whether a particular private well is affected requires sampling and investigation, not merely evidence of nearby foam use.

Portable extinguishers – stock and servicing: PFAS foam extinguisher rules distinguish first placing on the market in 2026, the special 2027 deadline for alcohol-resistant foam and continued use until the end of 2030. The site-specific 15-year plan does not automatically cover every portable device. See our guide to PFAS portable extinguishers, stock, servicing and replacement for a practical decision matrix.

Templates in this article

Explore the topic

Back to blog
Customers rate us 4.6/5 based on 10261 reviews.